Invers-Trennverstärker DB 6250<br />Inverse Isolation Amplifier DB 6250<br />
new
Goto Service Web Portal
Webinfo 4 Easy :: 112

Inverse Isolation Amplifier DB 6250

Isolation And Conversion Of Industrial Signals With Inverse Characteristic

With the configurable Inverse Isolation Amplifier DB 6250 DRAGO is extending its offer on high functional and high reliable components of the interface technique.

  • Easy realization of inverse transmission characteristic
    Inverse characteristic for unipolar and bipolar signals can be easily set by using DIP switch
  • Universal power supply for 20...253 V AC/DC
    Applicable world-wide for all common supply voltages
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Ultra small sized housing
    12.5 mm housing with plug-in screw terminal blocks
  • High bandwidth; high accuracy
    No distortion; no falsification of measured signal
  • Protective Separation
    Protects service personnel and downstream devices against impermissibly high voltage
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty

The Inverse Isolation Amplifier DB 6250 is used for isolation and conversion of bipolar and unipolar industrial signals with inverse characteristic. Due to the easy selection of the input and output ranges, the new universal power supply and the ultra small housing the Isolation Amplifier is suitable for flexible use. High reliability and Protective Separation are further characteristics that make the DB 6250 unrivaled.

The order key allows you to select the desired input and output ranges to which the unit will be adjusted at the factory before delivery. These can be easily reconfigured at any time by means of DIP switch settings. Subsequent readjustment or a measured range compensation can then be performed at the zero/scan potentiometers on the front panel. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.

The small housing with 12.5 mm width saves space in your switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly. For range setting a simple housing unblocking is installed which makes it possible to reach easily all control elements on the mounting rail.

The new universal power pack for 20 ... 253 V AC/DC means the DB 6250 can be used anywhere in the world, with all mains power supplies. The unit's high efficiency contributes significantly to reducing the unit's own heat generation. This is reflected in extremely high reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply.

Technical Data

Input

  Voltage Current
Input signals 1)
(terminal/switch selectable)
± 10 V, 0...10 V, 2...10 V
± 5 V, 0...5 V, 1...5 V
± 20 mA, 0...20 mA, 4...20 mA
± 10 mA, 0...10 mA, 2...10 mA
Input resistance
Approx. 1 MOhm Approx. 25 Ohm
Input capacitance
Approx. 1 nF Approx. 1 nF
Overload Voltage limitation via 30 V Z-Diode,
max. continuous current 30 mA
≤ 200 mA

Output

  Voltage Current
Output signals, inverse characteristic
(switch selectable) 1)
± 10 V, 0...10 V, 2...10 V
± 5 V, 0...5 V, 1...5 V
± 20 mA, 0...20 mA, 4...20 mA
± 10 mA, 0...10 mA, 2...10 mA
Load ≤ 10 mA (1 kOhm bei 10 V) ≤ 12 V (600 Ohm bei 20 mA)
Linear transmission range unipolar: –2 ... +110 %, bipolar: –110 ... +110 %
Ripple < 10 mV rms

General Data

Transmission error
0,1 % of final value
Temperature coefficient 2) 100 ppm/K final value
Zero/Span compensation
± 10 %
Cut-off frequency (-3 dB) > 10 kHz 1), switchable to < 30 Hz
Test voltage 4 kV, 50 Hz
Input against output against power supply
Working voltage 3)
(Basic Insulation)
Up to 1000 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
Protection against electrical shock 3) Protective separation according to EN 61140  by reinforced insulation in accordance with EN 61010-1 up to 600 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage
–20 °C to +70 °C
–35 °C to +85 °C
Power supply 20 ... 253 V AC/DC,
AC 48 ... 62 Hz, approx. 2 VA
DC approx. 1.0 W
EMC 4) EMVG, EN 61326 -1
Construction 12.5 mm housing, protection type: IP 20
Weight Approx. 100 g
  1. Factory setting , if no other information is given by ordering
  2. Average TC in specified operating temperature range
  3. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices
    in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  4. Minor deviations possible during interference

Block diagram

Db6200

Dimensions

GehaeuseHighFunctionality

Terminal assignments
Wire cross-section max. 2.5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)

1 Input + current
5 Output +
2 Input - current
6 Output -
3 Input + voltage 7 Power supply ~
4 Input - voltage 8 Power supply ~

Product line

Device Order No.
Inverse Isolation Amplifier     DB 6250 AG -
XX - XX
(Factory default setting,
reconfigurable any time by
using DIP-switch)
Input ± 10 V   00  
0 ... 10 V   01  
2 ... 10 V   02  
± 5 V   03  
0 ... 5 V   04  
1 ... 5 V   05  
± 20 mA   06  
0 ... 20 mA   07  
4 ... 20 mA   08  
± 10 mA   09  
0 ... 10 mA   10  
2 ... 10 mA   11  
Output ± 10 V     00
0 ... 10 V     01
2 ... 10 V     02
± 5 V     03
0 ... 5 V     04
1 ... 5 V     05
± 20 mA     06
0 ... 20 mA     07
4 ... 20 mA     08
± 10 mA     09
0 ... 10 mA     10
2 ... 10 mA     11
Example:
Inverse Isolation Amplifier,
Input ± 5 V, Output 4 ... 20 mA
 
DB 6250 AG -
 
03 -
 
08
If no information is given by ordering, the devices are delivered with the standard configuration:
Input signal ±10 V, Output signal ±10 V.
Subject to change!

Go back

Customer Request at DRAGO
Contact details:




Your question: