<p>Passiver Speisetrenner DC 58<br />Transmitter Repeater DC 58</p>
Goto Service Web Portal
Webinfo 4 Easy :: 202

Transmitter Repeater DC 58

Powering and Isolation of 2-wire transmitters

With its introduction into the Tiny Snap Series of the Transmitter Repeater DC 58, DRAGO has further expanded its product offerings in the area of compact and economical interface technology compo-nents.

  • Cost optimized design
    Economical separation for standard applications
  • Only 60 mm installation depth, 11.2 mm wide
    Can be installed in economical standard terminal boxes
  • Galvanic isolation across input and output
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • High reliability and long-term stability
    New APT technology for signal processing
  • Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • No power supply required
    Saving costs since wiring is reduced and line influences are omitted
  • 5 Years Warranty

The Transmitter Repeater DC 58 is used for powering of 2-wire transmitters. The 24 V power from the control system is galvanic isolated transferred to the 2-wire transmitter with small voltage drop. Its high level of reliability, extremely compact form, and cost optimized design make the DC 58 the first choice in its class!

Numerous sensible details: For example, because of its extremely small installation depth of only 60 mm, the DC 58 can also be installed in economical standard terminal boxes such as those frequently used for decentralized measuring points. The slim housing with 11.2 mm wide for one or two channels saves significant space on the DIN-rail.

Analog signal processing utilizing the new APT technology guarantees precise measured values with short response times and outstanding signal reproduction at the output – and all this with unparallel sturdiness and long-term stability of the insulation paths under tough industrial conditions.

To protect both maintenance personnel as well as downstream equipment against impermissibly high voltages, the DC 58 offers Protective Separation in according to EN 61140. The DC 58 requires no additional power supply since the auxiliary power is obtained from the current loop without distorting it. This not only saves costs during installation, but also increases reliability.

Technical Data

Input

Input signal 4 ... 20 mA
Operating current range 3 ... 23 mA
Voltage drop < 4,7 V
Short circuit input current < 50 mA

Output

Output signal 4 ... 20 mA
Supply voltage 15 ... 30 V DC
Response time Approx. 50 ms
Ripple < 10 mVrms

General Data

Transmission error < 0.2 %
Load error < 0.01 % of final value / V
Temperature coefficient 1) < 0.015 % / K of final value
Test voltage 2.5 kV, 50 Hz
Working voltage 2)
(Basic Insulation)
Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010–1.
Protection against electrical shock 2) Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010–1 up to 300 V AC/DC for overvoltage category II and pollution degree 2.
Ambient temperature Operation
Transport and storage
    0 °C to +55 °C
–25 °C to +80 °C
EMC 3) EN 61326 -1
Construction 11.2 mm housing, protection classt: IP 20
Weight Approx. 50 g
  1. Average TC in specified operating temperature range
  2. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference

Block diagram

Dc58

Dimensions

GehaeuseTiny

Terminal assignments
Wire cross-section max. 2.5 mm²

1 Input + 5 Output +
2 Input - 6 Output -

Product line

Devices Order No.
Transmitter Repeater DC 58 DC 58 K
Subject to change!