Shunt-Trennverstärker DS 7200<br />Isolation Amplifier DS 7200
Goto Service Web Portal
Webinfo 4 Easy :: 109

Shunt Isolation Amplifier DS 7200

Isolation and Conversion of Bipolar and Unipolar mV–Signals

With the Isolation Amplifier for Shunt Voltages DS 7200 DRAGO is extending its offer on high functional and high reliable components of the interface technique.

  • Easy selection of input and output range
    Input and output range for unipolar and bipolar signals can be easily set by using DIP switch
  • Universal power supply for 20 ... 253 V AC/DC
    Applicable world-wide for all common supply voltages
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Ultra small sized housing
    12.5 mm housing with plug-in screw terminal blocks
  • High bandwidth; high accuracy
    No distortion; no falsification of measured signal
  • Protective Separation
    Protects service personnel and downstream devices against impermissibly high voltage
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty

The Shunt Isolation Amplifier DS 7200 is used for separation and conversion of bipolar and unipolar mV-signals such as those frequently used for current measuring with shuntresistors or other applications. Due to the easy selection of the input and output ranges, the new universal power supply and the ultra small housing the Isolation Amplifier is suitable for flexible use. High reliability and Protective Separation are further characteristics that make the DS 7200 unrivaled.

The order key allows you to select the desired input and output ranges to which the unit will be adjusted at the factory before delivery. These can be easily reconfigured at any time by means of DIP switch settings. Subsequent readjustment or a measured range compensation can then be performed at the zero/span potentiometers on the front panel. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.

The slim housing with 12.5 mm width saves space in your switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly. For range setting a simple housing unblocking is installed which makes it possible to reach easily all control elements on the DIN-rail.

The new universal power pack for 20...253 V AC/DC means the DS 7200 can be used anywhere in the world, with all mains power supplies. The unit’s high efficiency contributes significantly to reducing the unit’s own heat generation. This is reflected in extremely high reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply.

Technical Data

Input

Input signals
(terminal/switch selectable)

± 60 mV, ± 100 mV, ± 150 mV, ± 250 mV, ± 300 mV, ± 500 mV
0...60 mV, 0...100 mV, 0...150 mV, 0...250 mV, 0...300 mV, 0...500 mV
Input resistance
> 100 kOhm
Input capacitance Approx. 1 nF
Overload ≤ 30 V

Output

  Voltage Current
Output signals
(switch selectable)
± 10 V, 0...10 V, 2...10 V
± 5 V, 0...5 V, 1...5 V
± 20 mA, 0...20 mA, 4...20 mA
± 10 mA, 0...10 mA, 2...10 mA
Load ≤ 10 mA (1 kOhm at 10 V) ≤ 12 V (600 Ohm at 20 mA)
Linear transmission range
unipolar: –2 ... +110 %, bipolar: –110 ... +110 %
Ripple < 20 mVrms

General data

Transmission error 0,1 % of final value
Temperature coefficient  2) 100 ppm/K of final value
Zero/Span compensation ± 10 %
Cut-off frequency (-3 dB) > 10 kHz  1), switchable to < 30 Hz
Test voltage 4 kV, 50 Hz
Input against output against power supply
Working voltage 3)
(Basic Insulation
Up to 1000 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
Protection against electrical shock 3) Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 600 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperature Operation
Transport and storage
–20 °C to +70 °C
–35 °C to +85 °C
Power supply 20 ... 253 V AC/DC,
AC 48...62 Hz, approx. 2 VA
DC approx. 1.0 W
EMC 4) EMVG, EN 61326 -1
Construction 12.5 mm housing, protection class: IP 20
Weight Approx. 100 g
  1. Factory setting, if no other information is given by ordering
  2. Average TC in specified operating temperature range
  3. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  4. Minor deviations possible during interference

Bold: Factory setting, if no other information is given by ordering

Block diagram

Ds7200

Dimensions

GehaeuseHighFunctionality

Terminal assignments
Wire cross-section max. 2,5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)

1 Input + 5 Output +
2 Input - 6 Output -
3 Input + 7 Power supply ~
4 Input - 8 Power supply ~

Product line

Devices Order No.
Shunt Isolation Amplifier  DS 7200
DS 7200 AG -
XX -
XX
(Factory default setting,
reconfigurable any time by
reconfigurable any time by
Input ± 60 mV   50  
0 ... 60 mV   51  
± 100 mV   52  
0 ... 100 mV   53  
± 150 mV   54  
0 ... 150 mV   55  
± 250 mV   56  
0 ... 250 mV   57  
± 300 mV   58  
0 ... 300 mV   59  
± 500 mV   60  
0 ... 500 mV   61  
Output ± 10 V     00
0 ... 10 V     01
2 ... 10 V     02
± 5 V     03
0 ... 5 V     04
1 ... 5 V     05
± 20 mA     06
0 ... 20 mA     07
4 ... 20 mA     08
± 10 mA     09
0 ... 10 mA     10
2 ... 10 mA     11
Example:
Shunt Isolation Amplifier,
Input ± 150 mV, Output 4 ... 20 mA

DS 7200 AG -

54 -

08
If no information is given by ordering, the devices are delivered with the standard configuration: Input signal ± 60 mV, Output signal ±10 V.
Subject to change!

Go back

Customer Request at DRAGO
Contact details:




Your question: