Isolation Amplifier DN 2400

Isolation and Conversion of Standard Signals in Low-cost Applications

With the Isolation Amplifier DN 2400 DRAGO offers a cheap alternative for industrial standard applications.

  • Cost optimized design
    Economical separation for standard applications
  • Calibrated signal setting
    Input and output range can be set by using DIP switch – without any further adjustment
  • Universal power supply for 20...253 V AC/DC
    Applicable world-wide for all common supply voltages
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Ultra-small-sized housing
    12.5 mm housing with plug-in screw terminal blocks
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty

The Isolation Amplifier DN 2400 is used for isolation and conversion of 0...20 mA, 4...20 mA and 0...10 V standard signals. Its high level of reliability and cost optimized design make the DN 2400 the first choice in its class!

Unique in its price class, the DN 2400 provides application flexibility thanks to the calibrated range selection and the new universal power pack.

The desired input and output range can be easily set by using DIP switch and due to the calibrated range selection no further adjustment is necessary.

The slim housing with 12.5 mm width saves space in the switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly. For range selection a simple housing unblocking is installed which makes it possible to reach easily all control elements on the mounting rail.

In cause of the new universal power supply for 20...253 V AC/DC the Isolation Amplifier DN 2400 is applicable world-wide for all common supply voltages.

Technical Data

Input

Input signal 1)
0...20 mA, 4...20 mA, 0...10 V
terminal/switch selectable
Input resistance Current input
Voltage input
approx. 22 Ohm
approx. 1 MOhm
Overload Current input
Voltage input
≤ 200 mA
Voltage limitation via 30 V Z-Diode, max. continuous current 30 mA

Output

Output signal 0...20 mA, 4...20 mA, 0...10 V, umschaltbar
Load Current output
Voltage output
≤ 10 V (500 Ohm at 20 mA)
≤ 10 mA (1 kOhm at 10 V)
Offset 20 µA / 10 mV
Ripple < 20 mVrms

General Data

Transmission error 0.3 % of measured value
Temperature coefficient 2) 150 ppm/K of final value
Cut-off frequency (-3 dB) 1 kHz
Test voltage 2.5 kV, 50 Hz
Input against output against power supply
Working voltage 3)
(Basic Insulation)
Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
Ambient temperature Operation
Transport and storage
–10 °C to +60 °C
–20 °C to +80 °C
Power supply 20 ... 253 V AC/DC,
AC 48 ... 62 Hz, approx. 3 VA
DC approx. 1.5 W
EMC 4) EMVG, EN 61326 -1
Construction 12.5 mm housing, protection type: IP 20
Weight Approx. 100 g
  1. Factory setting
  2. Average TC in specified operating temperature range
  3. As far as practicable the standards and rules mentioned above are considered by development and production of our devices. In addition the assembly rules for our devices are to be considered by installation in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  4. Minor deviations possible during interference

Bold: Factory setting for DN 2400 AG

Block diagram

Dn2400

Dimensions

GehaeuseHighFunctionality
Terminal assignments

Wire cross-section max. 2.5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)

1 Input + current 5 Output +
2 Input - current 6 Output -
3 Input + voltage 7 Power supply ~
4 Input - voltage 8 Power supply ~

Product line

Devices Order No.
Isolation Amplifier, calibrated range selection DN 2400 AG