Normsignal-Trennverstärker DN 240M<br />Isolation Amplifier DN 240M
new
Goto Service Web Portal
Webinfo 4 Easy :: 501

Isolation Amplifier Module DN 240M

Isolation And Conversion Of Standard Signals for PCB Assembling

With the Isolation Amplifier DN 240M DRAGO offers a cheap alternative for industrial standard applications.

  • Cost optimized design
    Economical separation for standard applications
  • Calibrated signal setting
    Input and output range can be set by using connector pins - without any further adjustment
  • Power Supply for 24 V DC
    Applicable for standard power supply voltages
  • 3-port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Ultra-small-sized housing
    15.5 mm flat module for pcb assembling
  • Maximum reliability
    No maintenance costs
  • 5 Years Warranty

The Isolation Amplifier DN 240M is used for isolation and conversion of 0 ... 20 mA, 4 ... 20 mA and 0 ... 10 V standard signals. Its high level of reliability and cost optimized design make the DN 240M the first choice in customer applications.

Unique in its price class, the DN 240M provides application flexibility thanks to the calibrated range.

The desired input and output range can be easily set by terminal pins and due to the calibrated range selection no further adjustment is necessary.

The flat module with 15.5 mm height for pcb assembling saves space in the customer application.

Technical Data

Input

Input signal
0...20 mA, 4...20 mA, 0...10 V
terminal selectable
Input resistance
Current input
Voltage input
22 Ohm
1 MOhm
Overload Current input
Voltage input
≤ 100 mA
Voltage limitation via 30 V Z-Diode, max. continuous current 30 mA

Output

Output signal
0...20 mA, 4...20 mA, 0...10 V,
terminal selectable
Load Current output
Voltage output
≤ 10 V (500 Ohm @ 20 mA)
≤ 10 mA (1 kOhm @ 10 V)
Offset 20 µA / 10 mV
Ripple < 20 mV rms

General Data

Transmission error
0.3 % of measured value
Temperature coefficient 1) 150 ppm/K of final value
Cut-off frequency (-3 dB) Approx. 1 kHz
Test voltage
2.5 kV, 50 Hz
Input against output against power supply
Working voltage 2)
(Basic Insulation)
Up to 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits.
Ambient temperature Operation
Transport and storage
–10 °C to +60 °C
–20 °C to +80 °C
Power supply 24 V DC ±10 %
DC approx. 1,2 W
EMC 3) EMVG, EN 61326 -1
Construction Module for pcb assembling, 52.5 x 36 x 15.5 mm (l x w x h)
Weight Approx. 60 g
  1. Average TC in specified operating temperature range
  2. As far as practicable the standards and rules mentioned above are considered by development and production of our devices. In addition the assembly rules for our devices are to be considered by installation in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference

Block diagram

Dn240

Dimensions

Modul dn240 e

Product line

Device Order No.
Isolation Amplifier Module, calibrated range selection DN 240M
Subject to change!