Monitoring of AC/DC Voltage
With the Voltage Measuring Contactor DG 3400 DRAGO is extending its offer on high-functional and high-reliable components of the interface technique.
- Easy selection of operating mode
MIN / MAX alarm and N.O. / N.C. contact can be easily set by using DIP switch - Relay with high power handling
SPDT relay with 6 A current switch capability - True 3-port separation
Protection against erroneous measurements due to parasitic voltages or ground loops - Switch state indicated by LED
Easy to adjust the set point and hysteresis - Protective Separation acc. to EN 50178
Protects service personnel and downstream devices against impermissibly high voltage - High reliability and long-term stability
No maintenance costs - Unlimited use with 24 V AC/DC power supply
Universally applicable for all measurement and industrial applications - 5 Years Warranty
The Voltage Measuring Contactor DG 3400 is used to monitor limit values of AC/DC voltages. High reliability and Protective Separation are essential characteristics that contribute to fault-free equipment operation.
Two switch channels can be separately configured. The switch point and the switch hysteresis can each be adjusted by means of their own 12-turn potentiometer located on the unit’s front panel. The switch state is indicated by a yellow LED.
The direction of effect and the mode of operation can be switched by means of DIP switch settings. Both switch outputs can be set up as either MIN or MAX alarms. The relay contacts switch high power loads either as N.O. or N.C. contacts.
Protective Separation and the 24 V AC/DC power supply make the DG 3400 universally applicable for all measurement and industrial applications, as well as for building automation.
Input
| Input signal | Measuring ranges: 24 V, 48 V, 120 V, 250 V, switchable Unipolar, bipolar or sinusoidal alternating current voltages, f = 10 ... 500 Hz |
| Input resistance | 1 MOhm |
| Overload | Max. 500 V, continuous |
| Set point range | 0 ... 100 % of input range with 12-turn potentiometer , MIN/MAX-Alarm switchable |
| Hystersis | 0 ... 60 % of final value with 12-turn potentiometer |
Output
| Contact type | 2 SPDT relays, mode of operation switchable |
| Switching capability | 250 V AC/DC, max. 6 A, max. 1500 VA |
| Switch state indicator | Yellow LED |
| Response time | DC: approx. 20 ms, AC: 500 ms |
General Data
| Set point error | 0,2 % of final value | |
| Temperature coefficient 1) | 150 ppm/K of final value | |
| Test voltage | 4 kV, 50 Hz, input against power supply against both relays 2.5 kV, 50 Hz, relay I against relay II |
|
| Working voltage 2) (Basic Insulation) |
Up to 600 V AC/DC for overvoltage category III and pollution degree 2 acc. to EN 50178 between input, power supply and relay outputs. Up to 300 V AC/DC between both relay outputs. |
|
| Protection against electrical shock 2) | Protective separation according to EN 50178 by reinforced insulation up to 300 V AC/DC for overvoltage category II and pollution degree 2 between input, power supply and relay outputs. | |
| Power supply | 24 V AC/DC, ± 15 % | AC: 48 ... 62 Hz, approx. 2 VA DC: approx. 1 W |
| Ambient temperature | Operation Transport and storage |
–20 °C to +60 °C –35 °C to +85 °C |
| EMC 3) | EN 61326 -1 | |
| Construction | 22.5 mm housing, protection class: IP 20 | |
| Weight | Approx. 100 g | |
- Average TC in specified operating temperature range.
- As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
- Minor deviations possible during interference.


Terminal assignments
| 7 | Input + | 11 | N/C |
| 8 | Input - | 9,10 | Output I |
| 12 | N/O | ||
| 1,2 | Power supply ~ |
||
| 3,4 | Power supply ~ | 15 | N/C |
| 13,14 | Output II |
||
| 16 | N/O |
| Devices | Order No. |
| Voltage Measuring Contactor DG 3400 | DG 3400 |