Practical Tips
Additional measuring option for process signals
The standard signal splitters from the High Functionality series can be configured as current or voltage outputs on the output side. This makes it possible to create a shunt for measuring the process variable in a 4 - 20 mA current loop using a 0 - 10 V scale. Without breaking the current loop, at output II you can observe the current measured value using a voltage indicator, a chart recorder or a DVM.