Isolation And Conversion Of Potentiometer Position Signals
With the configurable Potentiometer Transducer DR 4310 DRAGO is extending its offer on high functional and high reliable components of the interface technique.
- Easy selection of input and output range
Input and output range for unipolar and bipolar signals can be easily set by using DIP switch - Universal power supply for 20...253 V AC/DC
Applicable world-wide for all common supply voltages - 3-port isolation
Protection against erroneous measurements due to parasitic voltages or ground loops - Ultra small sized housing
12.5 mm housing with plug-in screw terminal blocks - High bandwidth; high accuracy
No distortion; no falsification of measured signal - Protective Separation
Protects service personnel and downstream devices against impermissibly high voltage - Maximum reliability
No maintenance costs - 5 Years Warranty
The Potentiometer Transducer DR 4310 is used for isolation and conversion of potentiometer position signals. Due to the easy selection of the input and output ranges, the new universal power supply and the ultra small housing the Isolation Amplifier is suitable for flexible use. High reliability and Protective Separation are further characteristics that make the DR 4310 unrivaled.
The order key allows you to select the desired input and output ranges to which the unit will be adjusted at the factory before delivery. These can be easily reconfigured at any time by means of DIP switch settings. Subsequent readjustment or a measured range compensation can then be performed at the zero/scan potentiometers on the front panel. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.
The small housing with 12.5 mm width saves space in your switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly. For range setting a simple housing unblocking is installed which makes it possible to reach easily all control elements on the mounting rail.
The new universal power pack for 20 ... 253 V AC/DC means the DR 4310 can be used anywhere in the world, with all mains power supplies. The unit's high efficiency contributes significantly to reducing the unit's own heat generation. This is reflected in extremely high reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply.
Input
| Input Signal |
Potentiometer, 500 Ohm ... 100 kOhm |
| Potentiometer connection |
3 wire connection |
| Input resistance |
Approx. 10 MOhm |
Output
| Voltage | Current | |
| Output signals (switch selectable) |
± 10 V, 0...10 V, 2...10 V ± 5 V, 0...5 V, 1...5 V |
± 20 mA, 0...20 mA, 4...20 mA ± 10 mA, 0...10 mA, 2...10 mA |
| Load | ≤ 10 mA (1 kOhm @ 10 V) | ≤ 12 V (600 Ohm @ 20 mA) |
| Linear transmission range |
unipolar: –2 ... +110 %, bipolar: –110 ... +110 % | |
| Ripple | < 10 mV rms |
|
General Data
| Transmission error |
< 0,1 % of final value |
|
| Temperature coefficient 1) | 100 ppm/K final value |
|
| Zero/Span compensation |
± 10 % |
|
| Cut-off frequency(-3 dB) |
> 1 kHz, switchable to < 30 Hz |
|
| Test voltage |
4 kV, 50 Hz, Input against output against power supply |
|
| Working voltage 2) (Basic Insulation) |
Up to 1000 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 between all circuits. | |
| Protection against electrical shock 2) | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 600 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. | |
| Ambient temperature | Operation Transport and storage |
–20 to +70 °C –35 to +85 °C |
| Power supply |
20...253 V AC/DC, |
AC 48...62 Hz, approx. 2 VA DC approx. 1.0 W |
| EMC 3) | EMVG, EN 61326-1 | |
| Construction | 12.5 mm housing, protection type: IP 20 | |
| Weight | Approx. 100 g | |
- Average TC in specified operating temperature range
- As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices
in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices. - Minor deviations possible during interference
Bold: factory setting


Terminal assignments
Wire cross-section max. 2.5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)
| 1 | Input, Wiper + |
5 | Output + |
| 2 | Input, Poti + |
6 | Output - |
| 3 | Input, Poti - |
7 | Power supply ~ |
| 8 | Power supply ~ |
| Devices | Order No. |
| Potentiometer Transducer, configurable | DR 4310 AG |