<p>Stromwächter DG 3300<br />Current Measuring Contactor DG 3300</p>
Goto Service Web Portal
Webinfo 4 Easy :: 402

Current Measuring Contactor DG 3300

Monitoring of 1/5 A AC/DC Current

With the Current Measuring Contactor DG 3300 DRAGO is extending its offer on high-functional and high-reliable components of the interface technique.

  • Easy selection of operating mode
    MIN / MAX alarm and N.O. / N.C. contact can be easily set by using DIP switch
  • Relay with high power handling
    SPDT relay with 6 A current switch capability
  • True 4-port separation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Switch state indicated by LED
    Easy to adjust the set point and hysteresis
  • Protective Separation acc. to EN 50178
    Protects service personnel and downstream devices against impermissibly high voltage
  • High reliability and long-term stability
    New APT technology, no maintenance costs
  • Unlimited use with 24 V AC/DC power supply
    Universally applicable for all measurement and industrial applications
  • 5 Years Warranty

The Current Measuring Contactor DG 3300 is used to monitor limit values of 0...1/5 A AC/DC current circuits. High reliability and Protective Separation are essential characteristics that contribute to fault-free equipment operation.

Two switch channels can be separately configured. The switch point and the switch hysteresis can each be adjusted by means of their own 12-turn potentiometer located on the unit’s front panel. The switch state is indicated by a yellow LED.

The direction of effect and the mode of operation can be switched by means of DIP switch settings. Both switch outputs can be set up as either MIN or MAX alarms. The relay contacts switch high power loads either as N.O. or N.C. contacts.

Protective Separation and the 24 V AC/DC power supply make the DG 3300 universally applicable for all measurement and industrial applications, as well as for building automation.

Technical Data

Input

Input signal DC: 0 ... 1 A, ± 1 A, 0 ... 5 A, ± 5 A
AC: 0 ... 1 A, 0 ... 5 A
sinusoidal alternating currents, f = 10 ... 500 Hz
Input resistance < 10 mOhm
Overload 2 x IN continuous, surge current: 100 A for 1 s
Set point range 0 ... 100 % of input range with 12-turn potentiometer , MIN/MAX-Alarm switchable
Hystersis 0 ... 60 % of final value with 12-turn potentiometer

Output

Contact type 2 SPDT relays, mode of operation switchable
Switching capability 250 V AC/DC, max. 6 A, max. 1500 VA
Switch state indicator Yellow LED
Response time DC: approx. 20 ms, AC: 500 ms

General Data

Set point error 0,2 % of final value
Temperature coefficient 1) 150 ppm/K of final value
Test voltage 4 kV, 50 Hz, input against power supply against both relays
2.5 kV, 50 Hz, relay I against relay II
Working voltage 2)
(Basic Insulation)
Up to 600 V AC/DC for overvoltage category III and pollution degree 2 acc. to EN 50178 between input, power supply and relay outputs.
Up to 300 V AC/DC between both relay outputs.
Protection against electrical shock 2) Protective separation according to EN 50178 by reinforced insulation up to 300 V AC/DC for overvoltage category II and pollution degree 2 between input, power supply and relay outputs.
Power supply 24 V AC/DC, ± 15 % AC: 48 ... 62 Hz, approx. 2 VA
DC: approx. 1 W
Ambient temperature Operation
Transport and storage
–20 °C to +60 °C
–35 °C to +85 °C
EMC 3)
EN 61326 -1
Construction 22.5 mm housing, protection class: IP 20
Weight Approx. 100 g
  1. Average TC in specified operating temperature range.
  2. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference.

Block diagram

Dg3300

Dimensions

GehaeuseLimiter

Klemmenbelegung

5 Input + 11 N/C
8 Input - 9,10 Output I
    12 N/O
1,2 Power supply ~
   
3,4 Power supply ~ 15 N/C
    13,14 Output II
    16 N/O

Product line

Devices Order No.
Current Measuring Contactor DG 3300 DG 3300
Subject to change!

Go back