<p>Grenzwertschalter DG 3200<br />Alarm Unit DG 3200</p>
Goto Service Web Portal
Webinfo 4 Easy :: 401

Alarm Unit DG 3200

Control and Monitor Standard Signals

With the Alarm Unit DG 3200 DRAGO is extending its offer on high-functional and high-reliable components of the interface technique.

  • Easy selection of operating mode
    MIN / MAX alarm and N.O. / N.C. contact can be easily set by using DIP switch
  • Relay with high power handling
    SPDT relay with 6 A current switch capability
  • True 3-port separation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Switch state indicated by LED
    Easy to adjust the set point and hysteresis
  • Protective Separation acc. to EN 50178
    Protects service personnel and downstream devices against impermissibly high voltage
  • High reliability and long-term stability
    No maintenance costs
  • Unlimited use with 24 V AC/DC power supply
    Universally applicable for all measurement and industrial applications
  • 5 Years Warranty

The Alarm Unit DG 3200 is used to monitor limit values and regulate simple automation processes in 0(4)...20 mA and 0...10 V standard signal circuits. High reliability and Protective Separation are essential characteristics that contribute to fault-free equipment operation.

Two switch channels can be separately configured. The switch point and the switch hysteresis can each be adjusted by means of their own 12-turn potentiometer located on the unit's front panel. The switch state is indicated by a yellow LED.

The direction of effect and the mode of operation can be switched by means of DIP switch settings. Both switch outputs can be set up as either MIN or MAX alarms. The relay contacts switch high power loads either as N.O. or N.C. contacts.

Protective Separation and the 24 V AC/DC power supply make the DG 3200 universally applicable for all measurement and industrial applications, as well as for building automation.

Technical Data

Input

Input signal 0(4)...20 mA, ± 20 mA, 0...10 V, ± 10 V
Input resistance Current input
Voltage input
Approx. 5 Ohm
Approx. 1 MOhm
Overload Current input
Voltage input
≤ 200 mA
≤ 250 V
Set point range 0 ... 100 % of input range with 12-turn potentiometer , MIN/MAX-Alarm switchable
Hystersis 0 ... 60 % of final value with 12-turn potentiometer

Output

Contact type 2 SPDT relays, mode of operation switchable
Switching capability 250 V AC/DC, max. 6 A, max. 1500 VA
Switch state indicator Yellow LED
Response time Approx. 20 ms

General Data

Set point error 0,2 % of final value
Temperature coefficient 1) 150 ppm/K of final value
Test voltage 4 kV, 50 Hz, input against power supply against both relays
2,5 kV, 50 Hz, relay I against relay II
Working voltage 2)
(Basic Insulation)
Up to 600 V AC/DC for overvoltage category III and pollution degree 2 acc. to EN 50178 between input, power supply and relay outputs. Up to 300 V AC/D between both relay outputs.
Protection against electrical shock 2) Protective separation according to EN 50178 by reinforced insulation up to 300 V AC/DC for overvoltage category II and pollution degree 2 between input, power supply and relay outputs.
Power supply 24 V AC/DC, ± 15 % AC: 48 ... 62 Hz, approx. 2 VA
DC: approx. 1 W
Ambient temperature Operation
Transport and  
storage
–20 °C to +60 °C
–35 °C to +85 °C
EMC 3) EN 61326-1
Construction 22.5 mm housing, protection class: IP 20
Weight Approx. 100 g
  1. Average TC in specified operating temperature range
  2. As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
  3. Minor deviations possible during interference

Block diagram

Dg3200

Dimensions

GehaeuseLimiter

Terminal assignments

5 Input + current
11 N.C.
6 Input - current
9,10
Output I
    12 N.O.
7 Input + voltage

8 Input - voltage 15 N.C.
    13,14 Output II
1,2 Power supply ~ 16 N.O.
3,4 Power supply ~    

Product line

Devices Order No.
Alarm Unit DG 3200 DG 3200
Subject to change!

Go back

Customer Request at DRAGO
Contact details:




Your question: